ETCSlaveStack.ChangeFMMU (METH)
METHOD ChangeFMMU
Changes a FMMU from the slave
Example:
pSlave^.ChangeFMMU(1, 0, wOutLength, 0, 7, 16#1100, 0, 2, 1); // Outputs
- InOut:
Scope
Name
Type
Comment
Input
uiNbrFMMUUINTThe number to change (1..16)
dwGlobalStartAddressDWORDonly used in manual mode, depnding of the master global settings
wLengthWORDLength of FMMU in Bytes
usiStartBitUSINTStartbit of FMMU
usiEndBitUSINTEndbit of FMMU
wPhysStartAddressWORDPhysical start adress
usiPhysStartBitUSINTPhysical start bit
usiAccessUSINTread bit 0 write bit 1
dwFlagsDWORDbit 0 channel enable