EcatStopCom (FB)

FUNCTION_BLOCK EcatStopCom EXTENDS AC500_EcatBase.EcmETrigExt

Function block to stop the communication of the assigned EtherCAT coupler

InOut:

Scope

Name

Type

Initial

Comment

Inherited from

Input

Execute

BOOL

FALSE

A rising edge starts the operation, the output Busy goes to TRUE. In the first cycle all other inputs are read and stored, afterwards they are ignored. A falling edge does not stop the operation. After Done = TRUE or Error = TRUE and Execute = FALSE all outputs will be reset.

AbbETrig

Output

Done

BOOL

FALSE

Operation is completed without error (while outputs Busy and Error are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE

AbbETrig

Busy

BOOL

FALSE

Operation is running (while outputs Done and Error are FALSE)

AbbETrig

Error

BOOL

FALSE

Operation is stopped with error (while outputs Busy and Done are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE. The output ErrorID gives more details about the error.

AbbETrig

Input

Device

IDeviceCM579EtherCAT

Coupler device

EcmETrigExt

Output

ErrorID

ERROR_ID

ERROR_ID.NO_ERROR

Error code describing error condition (ERROR_ID located in AC500_EcatBase)

EcmETrigExt

Input

ResetIO

BOOL

FALSE

Enable the reset of IOs of the assigned slot in the IO Images

Timeout

UDINT

0

Timeout in milliseconds until the EtherCAT master must be in communication state “Stop”

Output

AddErrNo

UDINT

0

Addition error code for detailed error description, will be set if ErrorID = ERROR_ID.ADDITIONAL_ERROR_INFO (16#31). Explanation of error codes can be found in Hilscher documentation: https://kb.hilscher.com/display/ECM3V0/EtherCAT+Master+V4, chapter 5