Parameters (PARAMS)

InOut:

Scope

Name

Type

Initial

Comment

Constant

NumberOfInputAssemblies

UINT

64

This is the number of input assemblies allocated by the scanner. Changing this may lead to unexpected/miss behavior of the stack.

NumberOfOutputAssemblies

UINT

64

This is the number of output assemblies allocated by the scanner. Changing this may lead to unexpected/miss behavior of the stack.

ParamTcpSlowingUserParameter

TIME

TIME#150ms

This time increases the messages send between user parameter itself and the forward open request. Some slaves have problems by sending them user parameter and forward open to fast. The TCP task on the adapter seems to be too slow.

ParamResetWaitTime

TIME

TIME#2s0ms

The starting communication is slowed with this time. Some slaves have problems with opening a connection fast after a reset. To give him additional time to get there internal stacks knowing, that the connection is closed.

ParamScanStartOfInstanceAssem

DWORD

100

With which ID of assemblies to scan should be started, when device scan is activated?

ParamScanLastOfInstanceAssem

DWORD

199

Which ID of assemblies in a scan is the last one to observe?

ParamScanMaxAssemScanners

UINT

10

Maximal number of connections established to different adapters at the same time in an active scan

ParamScanMaxConnectorsPushUpIn1Call

UINT

1

Maximal number of scanned adapter informations pushed to ide in one call.

ParamScanMaxAssemOnTargetPossible

UINT

50

Maximal number of scanned adapters assemblies possible.