PnioCntrlGetDevState (FB)
FUNCTION_BLOCK PnioCntrlGetDevState EXTENDS AbbETrig
Function block to get Slave Connection Information of a device
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
ExecuteBOOLFALSE
A rising edge starts the operation, the output Busy goes to TRUE. In the first cycle all other inputs are read and stored, afterwards they are ignored. A falling edge does not stop the operation. After Done = TRUE or Error = TRUE and Execute = FALSE all outputs will be reset.
AbbETrig
Output
DoneBOOLFALSE
Operation is completed without error (while outputs Busy and Error are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE
AbbETrig
BusyBOOLFALSE
Operation is running (while outputs Done and Error are FALSE)
AbbETrig
ErrorBOOLFALSE
Operation is stopped with error (while outputs Busy and Done are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE. The output ErrorID gives more details about the error.
AbbETrig
Input
SlotBYTE0
Slot number of assigned coupler
DevNameSTRING(PNIOCNTRL_GLOBALS.PNIO_DEVNAME_LEN)‘’
Name of the device (Station Name, e.g. ‘ci501-pn-03’)
Output
ErrorIDERROR_ID.NO_ERROR
Error code description
AddErrNoUDINT0
Additional error message
MacARRAY [1..6] OF BYTE
MAC
IpDWORD0
IP address
VendorWORD0
Vendor ID
DeviceWORD0
Device ID
AlarmBOOLFALSE
Alarm pending, output not yet supported! Until complete clarification of diagnosis! (Always: FALSE)
ActiveBOOLFALSE
Device is currently registered as active
FlagsDWORD0
Status flags, see documentation