PnioCntrlGetDevIM0Data (FB)

FUNCTION_BLOCK PnioCntrlGetDevIM0Data EXTENDS AbbETrig

Access to the Identification and Maintenance Information of a certain PROFINET bus device FB uses PnioCntrlRead function block

InOut:

Scope

Name

Type

Initial

Comment

Inherited from

Input

Execute

BOOL

FALSE

A rising edge starts the operation, the output Busy goes to TRUE. In the first cycle all other inputs are read and stored, afterwards they are ignored. A falling edge does not stop the operation. After Done = TRUE or Error = TRUE and Execute = FALSE all outputs will be reset.

AbbETrig

Output

Done

BOOL

FALSE

Operation is completed without error (while outputs Busy and Error are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE

AbbETrig

Busy

BOOL

FALSE

Operation is running (while outputs Done and Error are FALSE)

AbbETrig

Error

BOOL

FALSE

Operation is stopped with error (while outputs Busy and Done are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE. The output ErrorID gives more details about the error.

AbbETrig

Input

Slot

BYTE

0

Slot number of assigned coupler

DevName

STRING(PNIOCNTRL_GLOBALS.PNIO_DEVNAME_LEN)

‘’

Name of the device (Station Name, e.g. ‘ci501-pn-03’)

DevSlot

WORD

0

Slot

Output

ErrorID

ERROR_ID

ERROR_ID.NO_ERROR

Error code description

AddErrNo

UDINT

0

Additional error message

VendorId

WORD

0

Unique ID indentifying the vendor of the device

OrderId

STRING(20)

‘’

Ordering information of the device

SerNo

STRING(16)

‘’

Serial number of the device

HwRev

WORD

0

Hardware revision

SwRev

PnioImSwRevType

Software revision

RevCnt

WORD

0

Hardware revision count

ProfileId

WORD

0

IO Device profile

ProfileSpec

WORD

0

IO Device profile variation

ImVersion

PnioImVersionType

Version of the implemented identification and maintence functions

ImSupported

WORD

0

Supported information and maintence messages