UpdateDiagnosisEntry
(FB)
FUNCTION_BLOCK UpdateDiagnosisEntry
This function block is used by a Profinet-Device application to add and remove Profinet diagnosis-data.
The description of ChannelDiagnosisData gives an example how to define device specific diagnosis messages within the GSDML.
The device application adds or removes diagnosis information according to the status of its real periphery.
The real periphery is specified through the diagnosis source (API, Slot, Subslot, Channel, Direction, Accumulative).
A diagnosis information (ChannelErrorType, optionally ExtChannelErrorType) exist only once per diagnosis source.
If severity or ExtChannelErrorAddValue changes, the diagnosis information is updated regarding these values.
If the diagnosis of a particular submodule changes during operation (submodule is in data-exchange), a diagnosis alarm is issued to the IO controller owning this submodule.
Update Diagnosis
PROGRAM PLC_PRG VAR ID : UDINT; exec : BOOL; // trigger execution of function block by setting exec := TRUE appears : BOOL := TRUE; updateDiag : ProfinetCommon.UpdateDiagnosisEntry; END_VAR ID := CommFB.SUBSLOT_ID(EN := TRUE, ID := PN_Device.DeviceID, SLOT := 2, SUBSLOT := 1); updateDiag.ID := ID; updateDiag.xAppears := appears; updateDiag.ChannelNumber := 1; updateDiag.ChannelProperties.ChannelType := ProfinetCommon.ChannelProperties_Type.BitSize1; updateDiag.ChannelProperties.Direction := ProfinetCommon.DiagnosisDirection.In; updateDiag.Diagnosis.Severity := ProfinetCommon.DiagnosisSeverity.Fault; updateDiag.Diagnosis.ChannelErrorType := ProfinetCommon.ChannelErrorType.Line_break; //0x0006 Line break updateDiag(xExecute := exec); IF(updateDiag.xDone OR updateDiag.xError) THEN exec := FALSE; END_IF
- InOut:
Scope
Name
Type
Initial
Comment
Input
xExecute
BOOL
Rising edge: Execute update of submodule’s diagnosis
ID
UDINT
Submodule-ID
xAppears
BOOL
TRUE: Diagnosis appears - add new diagnosis or update Severity and additional valueFALSE: Diagnosis disappears - clear diagnosis specified by source(Submodule, Channel) and error/ext-errorChannelNumber
UINT
16#8000
The channel number of the diagnosis source (0x8000 means the whole submodule)
ChannelProperties
additional channel data, not used for diagnosis that affect the whole submodule.
Diagnosis
The diagnosis-data entry
Output
xDone
BOOL
Action successfully completed
xBusy
BOOL
Function block active
xError
BOOL
error occurred, function block aborts action
Status
Error related to local update of diagnosis data, e.g. duplicate entry, no ressource…
PNIOStatus
UDINT