DP_AINFO
(STRUCT)
TYPE DP_AINFO : STRUCT
Alarm information of a profibus device (see: RALARM).
(see IEC 61158-6)
- InOut:
Name
Type
Comment
D_LEN
BYTE
Length of the alarm information: 4 .. 63 bytes
ATYPE
BYTE
Alarm Type
SLOT
BYTE
Slot number
ASPEC
BYTE
Alarm Specifier
Bit 0 to 1:0: no further differentiation1: Alarm appears and the related module is disturbed2: Alarm disappears and the related module has no further errors3: Alarm disappears and the related module is still disturbedBit 2: Additional acknowledgeBit 3 to 7: Sequence number of alarmADD_INFO
ARRAY [0..58] OF BYTE