CM592StateBits (STRUCT)
TYPE CM592StateBits : STRUCT
PROFIBUS master status data, master main error info
- InOut:
Name
Type
Initial
Comment
ControlErrorBOOLFALSE
Control error - caused by incorrect parameterization
AutoClearBOOLFALSE
Auto clear error - device stopped communication to all slaves and reached the auto-clear state
NoExchangeBOOLFALSE
Non exchange error - at least one slave has not reached the data exchange
FatalErrorBOOLFALSE
Fatal error - severe bus error, no bus communication is possible
NotReadyBOOLFALSE
Host not ready notification - host program is not ready to communicate
TimeoutBOOLFALSE
Timeout error - device timeout supervision has detected timeout violation because of rejected PROFIBUS telegrams - indicates bus short circuits