CD522PwmOut (FB)
FUNCTION_BLOCK CD522PwmOut EXTENDS AbbLConCA
Function block to access all IO-Values for the PWM-Output of CD522. This FB is valid to be used with mode 2 in channel configuration
- InOut:
Scope
Name
Type
Initial
Comment
Input
ChnNumWORD0
0 or 1, use output channel O0 or O1
EnPwmBOOLFALSE
Enable (TRUE) or disable (FALSE) the PWM output of the module
FreqDWORD0
Frequency of the PWM in Hertz from 0 to 100.000 Hz
DutyCycleWORD0
Duty cyle from 0 to 1000 (0 to 100.0%), percentage PWM signal is high
AdrInPOINTER TO WORD
0
Address of process image input. See ../Structs/CD522In for more information about structure
AdrOutPOINTER TO WORD
0
Address of process image output. See ../Structs/CD522Out for more information about structure
Output
ErrorIDERROR_ID.NO_ERROR
Error code description