CM579PnioImplicitRead
(FB)
FUNCTION_BLOCK CM579PnioImplicitRead EXTENDS CM579PnioBase
Function block that implements acyclic read service. It has to be considered that the execution of the function block could take a few seconds when devices are not existing or not reachable.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
Execute
BOOL
FALSE
A rising edge starts the operation, the output Busy goes to TRUE. In the first cycle all other inputs are read and stored, afterwards they are ignored. A falling edge does not stop the operation. After Done = TRUE or Error = TRUE and Execute = FALSE all outputs will be reset.
AbbETrig2
Output
Done
BOOL
FALSE
Operation is completed without error (while outputs Busy and Error are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE
AbbETrig2
Busy
BOOL
FALSE
Operation is running (while outputs Done and Error are FALSE)
AbbETrig2
Error
BOOL
FALSE
Operation is stopped with error (while outputs Busy and Done are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE. The output ErrorID gives more details about the error.
AbbETrig2
Input
Device
AC500_IoDrvCM579Profinet.IDeviceCM579Profinet
instance of CM579-PNIO device
CM579PnioBase
Output
ErrorID
error code that describes occurred error
CM579PnioBase
AddErrorID
UDINT
additional description of error, meaning depends on value of output ErrorID
CM579PnioBase
Input
DevIPAddr
UDINT
IP address of device
DevVendorID
UINT
Vendor ID of device
DevDeviceID
UINT
Device ID of device
DevInstanceID
UINT
Instance ID of device
DevApi
UDINT
API of submodule from which the data object is to be read
DevSlot
UINT
slot of submodule from which the data object is to be read
DevSubSlot
UINT
subslot of submodule from which the data object is to be read
DevIdx
UINT
index of data object to read
Data
POINTER TO BYTE
pointer to buffer where the read data will be copied to
DataMax
UINT
size of buffer provided at input Data
Output
StatusCode
UDINT
PROFINET status code of read service according to PROFINET specification
AddVal1
UINT
additional value 1 returned from PROFINET IO Device
AddVal2
UINT
additional value 2 returned from PROFINET IO Device
DataLen
UDINT
number of bytes that was read
Properties:
Job
Methods:
CheckInputs
PrepareJob
ResetOutputsAndMembers
SetOutputs
Structure: