PnioCntrlRead
(FB)
FUNCTION_BLOCK PnioCntrlRead EXTENDS AbbETrig
Read specific data from a device (RPC) through channel mailbox. No automatical sequenced packets, only single packets.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
Execute
BOOL
FALSE
A rising edge starts the operation, the output Busy goes to TRUE. In the first cycle all other inputs are read and stored, afterwards they are ignored. A falling edge does not stop the operation. After Done = TRUE or Error = TRUE and Execute = FALSE all outputs will be reset.
AbbETrig
Output
Done
BOOL
FALSE
Operation is completed without error (while outputs Busy and Error are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE
AbbETrig
Busy
BOOL
FALSE
Operation is running (while outputs Done and Error are FALSE)
AbbETrig
Error
BOOL
FALSE
Operation is stopped with error (while outputs Busy and Done are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE. The output ErrorID gives more details about the error.
AbbETrig
Input
Slot
BYTE
0
Slot number of assigned coupler
DevName
STRING(PNIOCNTRL_GLOBALS.PNIO_DEVNAME_LEN)
‘’
Name of the device (Station Name, e.g. ‘ci501-pn-03’ )
DevApi
DWORD
0
API
DevSlot
WORD
0
Slot
DevSubSlot
WORD
0
Sub slot
DevIdx
WORD
0
Index
Data
POINTER TO BYTE
0
Pointer to put data read to (via ADR operator)
DataMax
WORD
0
Max length of data
Output
ErrorID
ERROR_ID.NO_ERROR
Error code description
AddErrNo
UDINT
16#0
additional internal error code
Status
DWORD
0
PNIO code
AddVal1
WORD
0
Additional value 1
AddVal2
WORD
0
Additional value 2
DataLen
WORD
0
Number of bytes read to ADR(Data)