CM592SlaveDiagnosis
(FB)
FUNCTION_BLOCK PUBLIC CM592SlaveDiagnosis EXTENDS AC500_StateMachine.AbbETrig
Get detailed diagnosis of a connected slave according to PROFIBUS standard
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
Execute
BOOL
FALSE
A rising edge starts the operation, the output Busy goes to TRUE. In the first cycle all other inputs are read and stored, afterwards they are ignored. A falling edge does not stop the operation. After Done = TRUE or Error = TRUE and Execute = FALSE all outputs will be reset.
AbbETrig
Output
Done
BOOL
FALSE
Operation is completed without error (while outputs Busy and Error are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE
AbbETrig
Busy
BOOL
FALSE
Operation is running (while outputs Done and Error are FALSE)
AbbETrig
Error
BOOL
FALSE
Operation is stopped with error (while outputs Busy and Done are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE. The output ErrorID gives more details about the error.
AbbETrig
Input
Device
AC500_IoDrvCm592Profibus.IDeviceCM592Profibus
0
Reference to coupler device instance
SlaveAddr
USINT
0
Address of PROFIBUS slave device (0 - 126)
Output
ErrorID
ERROR_ID.NO_ERROR
Error code description
AddErrorID
UDINT
CM592Const.CM592_ADD_ERROR_NONE
Additional error info, in case ErrorID shows “REQUEST_FAILED”
Status_1
Stationstatus_1 according to PROFIBUS standard
Status_2
Stationstatus_2 according to PROFIBUS standard
Status_3
Stationstatus_3 according to PROFIBUS standard
MasterAddr
USINT
0
Bus address of assigned Master
ExtDiagLen
USINT
0
Length of extended diagnosis data following in ExtDiagData
ExtDiagData
Extended diagnosis data according to PROFIBUS standard