CM592SlaveDiagnosis (FB)
FUNCTION_BLOCK PUBLIC CM592SlaveDiagnosis EXTENDS AC500_StateMachine.AbbETrig
Get detailed diagnosis of a connected slave according to PROFIBUS standard
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
ExecuteBOOLFALSE
A rising edge starts the operation, the output Busy goes to TRUE. In the first cycle all other inputs are read and stored, afterwards they are ignored. A falling edge does not stop the operation. After Done = TRUE or Error = TRUE and Execute = FALSE all outputs will be reset.
AbbETrig
Output
DoneBOOLFALSE
Operation is completed without error (while outputs Busy and Error are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE
AbbETrig
BusyBOOLFALSE
Operation is running (while outputs Done and Error are FALSE)
AbbETrig
ErrorBOOLFALSE
Operation is stopped with error (while outputs Busy and Done are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE. The output ErrorID gives more details about the error.
AbbETrig
Input
DeviceAC500_IoDrvCm592Profibus.IDeviceCM592Profibus0
Reference to coupler device instance
SlaveAddrUSINT0
Address of PROFIBUS slave device (0 - 126)
Output
ErrorIDERROR_ID.NO_ERROR
Error code description
AddErrorIDUDINTCM592Const.CM592_ADD_ERROR_NONE
Additional error info, in case ErrorID shows “REQUEST_FAILED”
Status_1Stationstatus_1 according to PROFIBUS standard
Status_2Stationstatus_2 according to PROFIBUS standard
Status_3Stationstatus_3 according to PROFIBUS standard
MasterAddrUSINT0
Bus address of assigned Master
ExtDiagLenUSINT0
Length of extended diagnosis data following in ExtDiagData
ExtDiagDataExtended diagnosis data according to PROFIBUS standard