CM592Control (FB)
FUNCTION_BLOCK PUBLIC CM592Control EXTENDS AC500_StateMachine.AbbETrig
Send global control commands to a single or all slaves to synchronize process data.
Via using global control commands input or output data of slaves can be synchronized. The commands are selected by different combinations at inputs Freeze / Unfreeze and Sync / Unsync. The slave devices are selected by using individual slave addresses or broadcast address 127 and using PROFIBUS grouping functionality via input GroupSelect.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
ExecuteBOOLFALSE
A rising edge starts the operation, the output Busy goes to TRUE. In the first cycle all other inputs are read and stored, afterwards they are ignored. A falling edge does not stop the operation. After Done = TRUE or Error = TRUE and Execute = FALSE all outputs will be reset.
AbbETrig
Output
DoneBOOLFALSE
Operation is completed without error (while outputs Busy and Error are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE
AbbETrig
BusyBOOLFALSE
Operation is running (while outputs Done and Error are FALSE)
AbbETrig
ErrorBOOLFALSE
Operation is stopped with error (while outputs Busy and Done are FALSE). This output is TRUE for at least one cycle or until Execute is set to FALSE. The output ErrorID gives more details about the error.
AbbETrig
Input
DeviceAC500_IoDrvCm592Profibus.IDeviceCM592Profibus0
Reference to coupler device instance
SlaveAddrUSINT0
Address of PROFIBUS slave device (0 - 126 to acces single slaves or 127 to address group of slaves)
GroupSelectBYTE0
Select group of slaves, each bit represents a single group
UnfreezeBOOLFALSE
Command - unfreeze input data
FreezeBOOLFALSE
Command - freeze input data
UnsyncBOOLFALSE
Command - clear sync command
SyncBOOLFALSE
Command - freeze ouput data untill sync command is cleared again
Output
ErrorIDERROR_ID.NO_ERROR
Error code description
AddErrorIDUDINTCM592Const.CM592_ADD_ERROR_NONE
Additional error info, in case ErrorID shows “REQUEST_FAILED”