OBIOFreqOut
(FB)
FUNCTION_BLOCK OBIOFreqOut EXTENDS AbbLConCA
Access the PWM functionality for AC500 eco CPU and issue an adjustable frequency
- precondition
the respective channel is configured as PWM channel.
The block accepts Frequency in Hz. The frequency will be measured and adjusted, so that the average value meets the correct frequency, but single pulses can be longer or shorter.
The block counts the issued pulses. (rising edges are counted)
Note
This block should just be called once per cycle otherwise inconsistent values could be send to PRU, if send twice in short time.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
Enable
BOOL
FALSE
A rising edge (Enable = TRUE) starts the operation, the output Busy goes to TRUE. All other inputs are read and considered continuously. A falling edge (Enable = FALSE) aborts the operation. During Aborting the Busy is still TRUE. Afterward all outputs are reset.
AbbLConCA
Output
Busy
BOOL
FALSE
Operation is running (while output Error is FALSE)
AbbLConCA
Error
BOOL
FALSE
Operation is stopped with error (while output Busy is FALSE). This output is TRUE for at least one cycle or until Enable is set to FALSE. The output ErrorID gives more details about the error.
AbbLConCA
Input
Channel
BYTE
0
Channel, 0,1,2,3,4,5,6,7
Frequency
LREAL
[Hz] 0,05Hz..100kHz to switch the binary output on/off
Output
ErrorID
0
Error code
Counter
UDINT
number of pulses which were already issued, 32bit value counting modulo 2EXP32