CD522WriteOutput (FB)

FUNCTION_BLOCK CD522WriteOutput EXTENDS AbbLConCA

Function block to access all binary outputs of CD522.

InOut:

Scope

Name

Type

Initial

Comment

Inherited from

Input

Enable

BOOL

FALSE

A rising edge (Enable = TRUE) starts the operation, the output Busy goes to TRUE. All other inputs are read and considered continuously. A falling edge (Enable = FALSE) aborts the operation. During Aborting the Busy is still TRUE. Afterward all outputs are reset.

AbbLConCA

Output

Busy

BOOL

FALSE

Operation is running (while output Error is FALSE)

AbbLConCA

Error

BOOL

FALSE

Operation is stopped with error (while output Busy is FALSE). This output is TRUE for at least one cycle or until Enable is set to FALSE. The output ErrorID gives more details about the error.

AbbLConCA

Input

OutputO0

BOOL

FALSE

Binary output O0: have to be configured as “Digital output” not as “PWM” or “Pulse”

OutputO1

BOOL

FALSE

Binary output O1: have to be configured as “Digital output” not as “PWM” or “Pulse”

OutputC4

BOOL

FALSE

Binary output C4

OutputC5

BOOL

FALSE

Binary output C5

OutputC6

BOOL

FALSE

Binary output C6

OutputC7

BOOL

FALSE

Binary output C7

OutputC12

BOOL

FALSE

Binary output C12

OutputC13

BOOL

FALSE

Binary output C13

OutputC14

BOOL

FALSE

Binary output C14

OutputC15

BOOL

FALSE

Binary output C15

AdrOut

POINTER TO WORD

0

Address of process image output. See ../Structs/CD522Out for more information about structure

Output

ErrorID

ERROR_ID

ERROR_ID.NO_ERROR

Error code description